◆ MQK-25~50 suits large residential or small industrial and commercial scenarios.
◆ Supports 150% photovoltaic over-allocation, reducing grid demand and strengthening the independence of green energy.
◆ Adopts safe 200Ah lithium iron phosphate (LFP) battery, supporting 0.5C charge and discharge.
◆ Supports self-consumption, time-of-use electricity pricing, and backup power for diverse daily scenarios.
◆ Controls external loads like heat pumps, optimizing energy consumption.
◆ Suitable for scenarios with an unstable or absent power grid, such as micro power grids and isolated islands.
MQK-30k~50k
Inverter Parameters
Model | MQK-25 | MQK-30 | MQK-40 | MQK-50 | |
DC Input | |||||
Max.PV Aeray Power [Wp]@SIC | 37500 | 45000 | 60000 | 75000 | |
Max.DC Voltage [V] | 1000 | ||||
MPPT Voltage Range [V] | 200 850 | ||||
Rated DC Voltage[V] | 620 | ||||
Start Voltage[V] | 135 | ||||
Max.DC Input Current [A] | 4*30 | 4*30 | 4*30 | 4*30 | |
Max.DC Short Circuit Current [A] | 4*40 | 4*40 | 4*40 | 4*40 | |
Number of MPPT | 4 | 4 | 4 | 4 | |
Number of Strings per MPPT | 2 | 2 | 2 | 2 | |
Battery Parameters | |||||
Battery Typo | LiFeP04 | ||||
Battery Voltage Range [V] | 135 750 | ||||
Max.Charging/Diecharging Current [A] | 100-100 | ||||
AC Parameters [On gid] | |||||
Rated AC Power [W] | 25000 | 30000 | 40000 | 50000 | |
Maximum output apparent power [VA] | 27500 | 33000 | 44000 | 55000 | |
Maximum input apparent power [VA] | 30000 | 36000 | 48000 | 60000 | |
Maximum battery charging power [W] | 25000 | 30000 | 40000 | 50000 | |
Rated Voltage [V] | 3L/N/PE:220/380V:230/400V;240/415V | ||||
On-grid Frequency Dt] | 50/60 | ||||
Maximum current output [A] | 42 | 50 | 66 | 83 | |
Powor Factor | 0.Bloading 0.8lagging | ||||
Total Harmonic Distortion[THD] | <3%@rated powor | ||||
AC Parameters [Back up] | |||||
Rated AC Power [W] | 25000 | 30000 | 40000 | 50000 | |
Maximum output apparent power [VA] | 27500 | 33000 | 44000 | 55000 | |
Maximum current output [A] | 42 | 50 | 66 | 83 | |
UPS switching time | <20ms | <20ms | <20me | <20ms | |
Rated output voltage [V] | 3L/N/PE:220/380V;230/400V,240/415V | ||||
Rated Ac FrequencyDtr] | 50/60 | ||||
Output THDv@Liner Load) | <3% | ||||
AC Parameters[Generator] | |||||
Maximum input apparent power[VA] | 30000 | 36000 | 48000 | 60000 | |
Maximum battery charging power[W] | 25000 | 30000 | 40000 | 50000 | |
Rated output voltage[V] | 3L/N/PE:220/380V,230/400V;240/415V | ||||
Rated Ae Frequency Dtz] | 50/60 | ||||
Efficiency | |||||
Maximum PV conversion efficioncy | 98.8% | ||||
Euro Efficiency | 98.3% | ||||
Protection | Protecion | ||||
Battery input reversoconnection protection | Integrated | ||||
Insulation rotintance protection | Integrated | ||||
Surge protection | Integrated | ||||
Over-temperature protection | Integrated | ||||
Anti-islanding Protection | Integrated | ||||
Residual current protection | Integrated | ||||
AC aver-voltage protection | Integrated | ||||
Overload protection | Integrated | ||||
AC short-circuit protection | Integrated |
Model | MQK-25 | MQK-30 | MQK-40 | MQK-50 | |
General Parameters | |||||
Over voltage category | PV.II:Main:II | ||||
Dimensions(mm) | 800x620x300 | ||||
Weight (KG) | 72.0 | ||||
Protection degreo | IP65 | ||||
Standby sell-consumption(W) | <15 | ||||
Topology | Transformerloss | ||||
Operating Temperature Range("℃) | -30-60 | ||||
Relative Humidity(%) | 0-100 | ||||
Operating Altitude (m) | 3000(>3000m derating) | ||||
Cooling | Smart fan | ||||
Noise Level(dB) | <50 | ||||
Display | OLED & LED | ||||
Communcation | CAN,RS485,WFi/LAN(Optional) |
Model | CB2-62.9-HV5 | CB2-83.9-HV5 | CB2-104.9-HV5 |
Rated Energy [kWh] | 62.9 | 83.9 | 104.9 |
Usable Energy [kWh] | 56.6 | 75.5 | 94.4 |
Rated Capacity [Ah] | 205 | 205 | 205 |
No.of Modules | 6 | 8 | 10 |
Nominal Voltage[V] | 307.2 | 409.6 | 512 |
Voltage Range [V] | 240~350.4 | 320~467.2 | 400~584 |
Charge/Discharge Current [A] | 100 | 100 | 100 |
Rated Power [kW] | 30 | 40 | 50 |
Weight[kg] | 1030 | 1170 | 1310 |
Dimension[mm] | 960*1500*2000 (1185*1500*2000-include air condition) | ||
Communication | CAN | ||
Operating Temperature Range[C] | -30~50 | ||
Cooling Method | Air Conditioner | ||
Relative Humidity | 5~95%(non-condensing) | ||
Altitude [m] | 2000 | ||
Ingress Protection | IP54 | ||
Mounting | Ground-Mounted | ||
Control Module | CBC2-HV5 | ||
Weight[kg] | 30 | ||
Dimension[mm] | 870*603*204 | ||
Battery Module | CBU2-10.496-HV5 | ||
Rated Energy[kWh] | 10.496 | ||
Battery Module Serial Cell Quantity (pcs) | 16 | ||
Weight[kg] | 71 | ||
Dimension[mm] | 607*400*246 | ||
Applicable Standard | IEC62619-2017,UN38.3,IEC61000-6-2/4,IEC62477 |
Model | MQK-E3-6k-1p | MQK-E3-8k-1p | |||
Rated Power | 6000VA/6000W | 8000VA/8000W | |||
PVINPUT | |||||
Max power(kW) | 7 | 10 | |||
Max.DC voltage(V) | 500 | ||||
MPPTvoltagerange(V) | 90-450 | ||||
Max.inputcurrent(A) | 30 | 30 | |||
MPPT number/Max input strings number | 1/2 | 2/2 | |||
ACOUTPUT(GRID-TIED) | |||||
Grid voltage/range(V) | 230/90-280(For Personal Computers):170~280(For Home Appliances) | ||||
Frequency(Hz) | 50/60 | ||||
PF | 0.8lagqing-0.8leading | ||||
THDI | <3% | ||||
AC outputtopology | L+N+PE | ||||
BATTERY | + | ||||
Battery voltage ran ge(V) | 40-63 | ||||
Max.charging voltage(V) | 63 | ||||
Max.charge/discharge current(A)100/120 | 100/120 | ||||
Battery type | Lithium/Lead-acid | ||||
UPSOUTPUT | |||||
Rated power(kW) | 6 | 8 | |||
Rated outputvoltage(V) | 220/23 | 0/240 | |||
Rated output current(A) | 27.2/27/25 | 36.3/34,7/33.3 | |||
Rated frequency(Hz) | 50/60 | ||||
Transfer Time(ms) | <10 | ||||
THDu | <10% | ||||
Overload capacity | 5110%load10sz101%~110%load | ||||
PROTECTION&FEATURE | |||||
Anfiisland protection | Yes | ||||
Insulation monitoring | Yes | ||||
Residual currentmonitoring | Yes | ||||
Arc fault protection | Yes(Optional) | ||||
Parallel function | Yes,Sunits | ||||
Other protection | AC overument AC oraOvertemperature protection | ||||
GENERAL PARAMETER | |||||
Efficiency(Peak) | 93% | ||||
Degree of protection | IPS5 | ||||
Operation temperature | -25*C~50℃>45°Cderating | ||||
Cooling | smartcooling | ||||
Relative humidity | 5~95%(non-condensing) | ||||
Altitude | (>2000m Derating) | ||||
DimensionsWx DxH(mm) | 345*197*630 | ||||
Net Weight(Kg) | 22.5 | 32 | |||
Isolation transformer | No | ||||
Self-consumption(W) | <5 | ||||
DISPLAYAND COMMUNICATION | |||||
Display | Touch screen | ||||
Interface | Standard:RS232,CAN&RS485,Optional:WiFi,CT | ||||
Safety standard | ENIECS2109-1,ENIEOS2109-2 |